11 Supplement

VEGABAR 87 • Profibus PA

45047-EN-131107

Nominal measuring range in bar/kPa

Nominal measuring range

in psig

Long-term drift of the ze-

ro signal

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< (0.1 % x TD)/year

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.25 % x TD)/year

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (1 % x TD)/year

Ambient conditions

Version

Ambient temperature

Storage and transport temper-

ature

Version with connection tube

-40 … +80 °C (-40 … +176 °F)

-60 … +80 °C (-76 … +176 °F)

Version with suspension cable FEP -20 … +80 °C (-4 … +176 °F)

-20 … +80 °C (-4 … +176 °F)

Version IP 68 (1 bar) with connec-

tion cable PE

-20 … +60 °C (-4 … +140 °F)

-20 … +60 °C (-4 … +140 °F)

Process conditions
Product temperature

Ʋ Suspension cable

-12 … +100 °C (+10 … +212 °F)

Ʋ Connection tube

-12 … +100 °C (+10 … +212 °F)

Mechanical stress, depending on the instrument version
Vibration resistance

Ʋ Suspension cable

4 g at 5 … 200 Hz according to EN 60068-2-6 (vibration

with resonance)

Ʋ Connection tube

1 g (with lengths > 0.5 m (1.64 ft), the tube must be sup-

ported in addition)

Shock resistance

100 g, 6 ms according to EN 60068-2-27 (mechanical

shock)

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry

Ʋ Cable gland

M20 x 1.5

Ʋ Cable diameter (options)

5 … 9 mm (0.20 … 0.35 in)
6 … 12 mm (0.24 … 0.47 in)
10 … 14 mm (0.39 … 0.55 in)

Ʋ Cable entry

½ NPT

Ʋ Blind plug

M20 x 1.5; ½ NPT

Ʋ Closing cap

M20 x 1.5; ½ NPT

Plug options

Ʋ Signal circuit

Plug M12 x 1, according to ISO 4400, Harting HAN,

7/8" FF

Ʋ Indication circuit

M12 x 1 plug

Wire cross-section (spring-loaded terminals)