background image

30

6 Set up with the display and adjustment module

VEGABAR 87 • Profibus PA

45047-EN-131107

4. Units

In this menu item you determine the adjustment and temperature

units of the instrument. Depending on the selected application in the

menu item "Application", different adjustment units are available.

5. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
6. zero adjustment

In this menu item you carry out the zero adjustment for the processs

pressure.
Enter the respective pressure value for 0 %.
7. span adjustment

In this menu item you carry out the span adjustment for the processs

pressure
Enter the respective pressure value for 100 %.

5. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
6. Max. adjustment

In this menu item you carry out the max. adjustment for level
Enter the percentage value and the corresponding value for the max.

level.
7. Min. adjustment

In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.

level.

6.4 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

Quick setup - Process

pressure measurement

Quick setup - Level meas-

urement