8 Setup with PACTware

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44228-EN-130823

8 Setup with PACTware

8.1 Connect the PC

3

1

2

Fig. 28: Connection of the PC directly to the sensor via the interface adapter
1 USB cable to the PC

2 Interface adapter VEGACONNECT

3 Sensor

1

5

2 4

3

OPEN

TWIST

USB

LOCK

Fig. 29: Connecting the PC via HART to the signal cable
1 Sensor

2 HART resistance 250 Ω (optional depending on processing)

3 Connection cable with 2 mm pins and terminals

4 Processing system/PLC/Voltage supply

5 Interface adapter, for example VEGACONNECT 4

Note:

With power supply units with integrated HART resistance (internal

resistance approx. 250 Ω), an additional external resistance is not

necessary. This applies, e.g. to the VEGA instruments VEGATRENN

149A, VEGAMET 381, VEGAMET 391. Common Ex separators are

also usually equipped with a sufficient current limitation resistance. In

Via the interface adapter

directly on the sensor

Via the interface adapter

and HART