beautypg.com

VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod and cable probe - PFA insulated With SIL qualification User Manual

Page 38

background image

38

7 Set up with the display and adjustment module

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44228-EN-130823

correctly. If necessary, other measures must be taken to maintain the

safety function.

Here you can assign a suitable measurement loop name. Push the

"OK" key to start the processing. With the "+" key you change the sign

and with the "->" key you jump to the next position.
You can enter names with max. 19 characters. The character set

comprises:

Capital letters from A … Z

Numbers from 0 … 9

Special characters + - / _ blanks

In this menu item you select the distance unit and the temperature

unit.

With the distance units you can choose between m, mm and ft and

with the temperature units betwenn °C, °F and K.

In this menu item you can enter the probe length or have the length

determined automatically by the sensor system.
When choosing "Yes", then the probe length will be determined

automatically. When choosing "No", you can enter the probe length

manually.

In this menu item you can select which type of medium you want to

measure. You can choose between liquid or bulk solid.

In this menu item, you can select the application. You can choose

between level measurement and interface measurement. You can

also choose between measurement in a vessel or in a bypass or

standpipe.

Setup - Measurement

loop name

Setup - Units

Setup - Probe length

Setup - Medium type

Setup - Application