VEGA VEGAFLEX 82 4 … 20 mA_HART two-wire User Manual

Page 3

background image

3

Quick start

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

41829-EN-130612

1. In this menu item you can select the application.

2. In the menu item "Medium - Dielectric constant" you can define

the medium type (medium).

3. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

4. A "Linearization" is recommended for all vessels in which the

vessel volume does not increase linearly with the level - e.g. in a

horizontal cylindrical or spherical tank. Activate the appropriate

curve.

The sensor measures the distance from the sensor (reference plane)

to the product surface.

4

5

3

1

2

4

1

2

3

5

Fig. 3: Measuring ranges - VEGAFLEX 82
1 Reference plane

2 Probe length L

3 Measuring range

4 Upper dead band (in this area no measurement is possible)

5 Lower dead band (in this area no measurement is possible)

For this adjustment, the distance is entered when the vessel is full

and nearly empty. If these values are not known, an adjustment with

other distances, for example, 10 % and 90 % is also possible. Starting

point for these distance specifications is always the seal surface of

the thread or flange.

Parameterization example