VEGA VEGAFLEX 82 4 … 20 mA_HART two-wire User Manual
Page 19
19
4 Mounting
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
41829-EN-130612
Fig. 10: Mounting of the sensor with inflowing medium
The reference plane for the measuring range of the sensors is the
sealing surface of the thread or flange.
Keep in mind that a min. distance must be maintained below the refer-
ence plane and possibly also at the end of the probe - measurement
in these areas is not possible (dead band). The length of the cable
can be used all the way to the end only when measuring conductive
products. These blocking distances for different mediums are listed
in chapter "Technical data". Keep in mind for the adjustment that the
default setting for the measuring range refers to water.
The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical
data" or on the type label of the sensor.
If there is a risk of the cable probe touching the vessel wall during
operation due to product movements or agitators, etc., the measuring
probe should be securely fixed.
In the gravity weight there is an internal thread (M12), e.g. for an eye-
bolt (optional) - (article no. 2.27423).
Make sure that the probe cable is not completely taut. Avoid tensile
loads on the cable.
Avoid undefined vessel connections, i.e. the connection must be
either grounded reliably or isolated reliably. Any undefined change of
this requirement can lead to measurement errors.
Measuring range
Pressure
Fasten