6 Set up with the display and adjustment module

VEGAFLEX 86 • Profibus PA

44232-EN-130910

In another window you can carry out a reset of the two peak values

separately.

The respective min. and max. measured values are saved in the

sensor. The values are displayed in the menu item "Peak values Ad-

ditional".
This menu item displays the peak values of the electronics tempera-

ture as well as the dielectric constant.

In another window you can carry out a reset of the two peak values

separately.

The menu item "Echo curve" shows the signal strength of the echoes

over the measuring range in V. The signal strength enables an evalua-

tion of the quality of the measurement.

With the following functions you can zoom part sections of the echo

curve.

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "V"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. via downstream

indicating instruments or the input card of the control system.

Diagnostics - Peak values

Additional

Diagnostics - Echo curve

Diagnosis - Simulation