6 Setup

VEGASWING 66 • - Relay

43756-EN-130322

6 Setup

6.1 General information

The figures in brackets refer to the following illustrations.

In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)

can be detected. For products with lower density, you have to set the

switch to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and

adjustment elements:

Signal lamps (1, 2, 3)

DIL switch for mode adjustment - min./max. (4)

DIL switch for sensitivity adjustment (5)

Note:

For test purposes, immerse the tuning fork of VEGASWING 66 always

in liquids. Do not test the function of VEGASWING 66 with your hand.

This can damage the sensor.

6.2 Adjustment elements

4

1

5

3

2

R

Fig. 14: Oscillator - Relay output
1 Control lamp for fault indication (red)

2 Signal lamp for indication of the switching condition (yellow)

3 Signal lamp for indication of the operating condition (green)

4 Mode switch for selecting the switching behaviour (min./max.)

5 DIL switch for sensitivity adjustment

The instrument monitors the vibrating frequency, electronics tempera-

ture and internal instrument functions.

Function/Configuration

Control lamp (1) - fault

indication (red)