9 Supplement

9.1 Technical data

General data
Series

Module unit for mounting on carrier rails 35 x 7.5 acc. to

EN 50022/60715

Weight

125 g (4.02 oz)

Housing material

Polycarbonate PC-FR

Connection terminals

Ʋ Type of terminal

Screw terminal

Ʋ Max. wire cross-section

2.5 mm² (AWG 12)

Voltage supply
Operating voltage

20 … 253 V AC/DC, 50/60 Hz

Max. power consumption

2 W (8 VA)

Sensor input
Quantity

1 x NAMUR

Input type

Active (sensor power supply by VEGATOR 111)

Measured value transmission

Analogue 1.2/2.1 mA

Switching threshold

Ʋ On

1.5 mA

Ʋ Off

1.7 mA

Ʋ Tolerance

± 100 µA

Current limitation

Through internal resistance

Terminal voltage

8.2 V DC, ± 5 %

Internal resistance

1 kΩ, ± 1 %

Detection line break

≤ 0.05 mA

Detection shortcircuit

≥ 6.8 mA

Relay output
Quantity

1 x operating relay, 1 x fail safe relay (optional)

Contact

Floating spdt

Contact material

AgSnO2, hard gold-plated

Switching voltage

min. 10 mV DC, max. 250 V AC/60 DC

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacity

min. 50 mW, max. 500 VA, max. 54 W DC (with U less

than 40 V)

1)

Phase angle cos φ

≥ 0.7

Switch on/Switch off delay

Ʋ Basic delay

100 ms

1)

If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be

permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.