9 Supplement
VEGATOR 111 •
46105-EN-131217
9 Supplement
9.1 Technical data
General data
Series
Module unit for mounting on carrier rails 35 x 7.5 acc. to
EN 50022/60715
Weight
125 g (4.02 oz)
Housing material
Polycarbonate PC-FR
Connection terminals
Ʋ Type of terminal
Screw terminal
Ʋ Max. wire cross-section
2.5 mm² (AWG 12)
Voltage supply
Operating voltage
20 … 253 V AC/DC, 50/60 Hz
Max. power consumption
2 W (8 VA)
Sensor input
Quantity
1 x NAMUR
Input type
Active (sensor power supply by VEGATOR 111)
Measured value transmission
Analogue 1.2/2.1 mA
Switching threshold
Ʋ On
1.5 mA
Ʋ Off
1.7 mA
Ʋ Tolerance
± 100 µA
Current limitation
Through internal resistance
Terminal voltage
8.2 V DC, ± 5 %
Internal resistance
1 kΩ, ± 1 %
Detection line break
≤ 0.05 mA
Detection shortcircuit
≥ 6.8 mA
Relay output
Quantity
1 x operating relay, 1 x fail safe relay (optional)
Contact
Floating spdt
Contact material
AgSnO2, hard gold-plated
Switching voltage
min. 10 mV DC, max. 250 V AC/60 DC
Switching current
min. 10 µA DC, max. 3 A AC, 1 A DC
Breaking capacity
min. 50 mW, max. 500 VA, max. 54 W DC (with U less
than 40 V)
1)
Phase angle cos φ
≥ 0.7
Switch on/Switch off delay
Ʋ Basic delay
100 ms
1)
If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be
permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.