3 function chart "point level – VEGA VEGATOR 111 User Manual

Page 14

background image

14

6 Setup

VEGATOR 111 •

46105-EN-131217

is released. Please note that when line monitoring is deactivated, the

red signal lamp does not light up.
Note:

Keep in mind that downstream connected devices are activated dur-

ing the function test. This allows you to check the correct function of

the measuring system.

6.3 Function chart "Point level"

The following chart provides an overview of the switching conditions

depending on the set mode and the level.
Note:

The switching conditions in the tables are only valid if the mode

switch on the sensor is set to "Max.".

Sensor

Signal conditioning instrument

Level

Sensor

current

LED yel-

low

(output)

LED red

(failure)

Relay

Fail safe

relay (op-

tional)

approx.

2.1 mA

ON

ON

approx.

1.2 mA

OFF

ON

any

< 0.35 mA

> 6.8 mA

OFF

OFF

Sensor

Signal conditioning instrument

Level

Sensor

current

LED yel-

low

(output)

LED red

(failure)

Relay

Fail safe

relay (op-

tional)

approx.

1.2 mA

ON

ON

approx.

2.1 mA

OFF

ON

any

< 0.35 mA

> 6,8 mA

OFF

OFF

Overfill protection, point

level

Dry run protection, point

level