5 Setup
Electronics module • VEGABAR series 80
45054-EN-131119
5 Setup
5.1 Setup
After mounting a new electronics module and connecting to power
supply, the following data are loaded automatically from the meas. cell
electronics:
•
Instrument type
•
Serial number
•
Date of manufacture
•
Measuring range
•
Default
The instrument is generally ready for operation.
If you are using an electronics module without sensor serial number
or a "universal electronics module" from stock, you can load the
order-specific data into the sensor on site if required.
Information:
When loading on site, the file must first be downloaded from the Inter-
net (see "Load sensor data").
sensor are displayed after entering the serial number.
Below the order data you will find "Sensor data for Service-DTM" as
XML file. Load this file with "Save as" on your PC and transfer it then
via PACTware and the Service DTM to the sensor.
As a rule, settings already carried out on site with the previous elec-
tronics module, such as min./max. adjustment etc., must be repeated.
Tip:
To do this, use the copy function of the display and adjustment mod-
ule or the adjustment software PACTware.
Load order-specific sen-
sor data
Adjustment