9 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART - four-wire

42280-EN-130314

Code
Text mes-

sage

Cause

Rectification

F260
Error in the

calibration

– Error in the calibration car-

ried out in the factory

– Error in the EEPROM

– Exchanging the electronics

– Send instrument for repair

F261
Error in the

instrument

settings

– Error during setup

– Error when carrying out a

reset

– False signal suppression

faulty

– Carry out a reset

– Repeat setup

F264
Installation/

Setup error

– Error during setup

– Check or correct installation

and/or parameter adjust-

ment

– Check probe length

F265
Measurement

function dis-

turbed

– Sensor no longer carries

out a measurement

– Carry out a reset

– Separate operating voltage

briefly

F266
Impermissi-

ble operating

voltage

– Operating voltage below

specified range

– Check electrical connection

– if necessary, increase

operating voltage

F267
No executable

sensor soft-

ware

– Sensor cannot start

– Exchanging the electronics

– Send instrument for repair

The following table shows the error codes and text messages in the

status message "Function check" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

C700
Simulation ac-

tive

– A simulation is active

– Finish simulation

– Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the

status message "Out of specification" and provides information on

causes as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

S600
Unpermissi-

ble electronics

temperature

– Temperature of the pro-

cessing electronics in the

non-specified section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

Function check

Out of specification