beautypg.com

VEGA VEGAFLEX 83 4 … 20 mA_HART - four-wire Polished version User Manual

Page 70

background image

70

11 Supplement

VEGAFLEX 83 • 4 … 20 mA/HART - four-wire

41840-EN-130314

Load (4 … 20 mA/HART - active)

< 500 Ω

Damping (63 % of the input variable)

0 … 999 s, adjustable

HART output values according to HART 7 (default setting)

2)

Ʋ First HART value (PV)

Linearised percentage value, level

Ʋ Second HART value (SV)

Distance to the level

Ʋ Third HART value (TV)

Measurement certainty, level

Ʋ Fourth HART value (QV)

Electronics temperature

Indication value - DIsplay and adjustment module

3)

Ʋ Displayed value 1

Filling height - Level

Ʋ Displayed value 2

Electronics temperature

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

4)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

5)6)

See following diagrams

2)

The output values can be assigned individually

3)

The indication values can be assigned individually

4)

with interface measurement = 2.0

5)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

6)

The dead bands can be optimizes by a false signal suppression.