VEGA SOLITRAC 31 Foundation Fieldbus User Manual
Page 39
39
6 Set up with the display and adjustment module
SOLITRAC 31 • Foundation Fieldbus
41781-EN-131119
Setup: Settings, e.g. for measurement loop name, isotope, applica-
tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,
simulation
Additional adjustments: Instrument unit, reset, date/time, copying
function
Info: Instrument name, hardware and software version, date of manu-
facture, instrument features
Check if the correct language is already set for the display. If not, you
can change the language in the menu item "Display/Language".
Start with the setup of SOLITRAC 31.
In the main menu point "Setup", the individual submenu points
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-
sible.
Setup
In this menu item you can adjust the SOLITRAC 31 to the integrated
isotope in the source container.
For this purpose, check which isotope is integrated in the source
container. You can find this information on the type label of the source
container.
With this selection, the sensitivity of the sensor is adapted in an opti-
mum way to the isotope.
The SOLITRAC 31 requires this information for the decay compensa-
tion. An annual recalibration is hence not necessary.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Enter here, the respective application.
Procedure
Setup - Isotope
Setup - Application