VEGA SOLITRAC 31 Foundation Fieldbus User Manual
Page 32
32
6 Set up with the display and adjustment module
SOLITRAC 31 • Foundation Fieldbus
41781-EN-131119
Because you have already set the background radiation to 0 in the
menu item: "Setup/Background radiation", the measured pulse rate
must be around 0 ct/s.
Show diagram
This menu item is only available if a linearization was already carried
out.
Show table
In this menu item you can show the individual value pairs of the
linearization.
Linearization - Delete
You can also delete individual linearization points.
Linearization - Modify
You can also modify individual linearization points.
In this menu item you can adjust the damping of the sensor. With
it you can suppress fluctuations in the measured value indication,
caused e.g. by an agitated product surface. This time can be between
1 and 1200 seconds. Keep in mind that the reaction time also in-
creases and the instrument reacts to quick level changes with a delay.
Generally a time of approximately 60 seconds is sufficient to smooth
the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable
damping on the basis of the adjustment and the measured value
changes. This setting is particularly suitable for application where fast
and slow level changes occur.
Setup - Damping