6 Set up with the display and adjustment module
SOLITRAC 31 • Foundation Fieldbus
41781-EN-131119
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
Note:
To carry out a simulation with the display and adjustment module,
you have to switch on the simulation switch on the electronics module
(switch position 1).
You can find the rotary switch on the electronics module in the elec-
tronics and connection department (large cover).
You can simulate different values:
Pulse rate of the sensor
Process value
Switching function of the relay
Information:
10 minutes after the key was pressed for the last time, the simulation
is interrupted automatically. You can also interrupt the simulation with
the switch on the electronics module.
Additional adjustments
In this menu item, the PIN is permanently activated/deactivated. Thus
you protect the sensor data against unauthorized access and unin-
tended changes. The default setting of the PIN is 0000.
This parameter is described in the operating instructions manual
"Display and adjustment module".
In this menu item you can set the actual date and time.
This parameter is described in the operating instructions manual
"Display and adjustment module".
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language and SIL.
Diagnosis - Simulation
Additional settings - PIN
Additional adjustments -
Date Time
Additional adjustments
- Reset