beautypg.com

VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Polished version User Manual

Page 82

background image

82

11 Supplement

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

41839-EN-130612

Gas phase

Temperature

Pressure

1 bar (14.5 psig)

10 bar (145 psig)

50 bar (725 psig)

Air

20 °C/68 °F

0.00 %

0.22 %

1.2 %

200 °C/392 °F

-0.01 %

0.13 %

0.74 %

400 °C/752 °F

-0.02 %

0.08 %

0.52 %

Hydrogen

20 °C/68 °F

-0.01 %

0.10 %

0.61 %

200 °C/392 °F

-0.02 %

0.05 %

0.37 %

400 °C/752 °F

-0.02 %

0.03 %

0.25 %

Steam (saturated

steam)

100 °C/212 °F

0.26 %

-

-

180 °C/356 °F

0.17 %

2.1 %

-

264 °C/507 °F

0.12 %

1.44 %

9.2 %

366 °C/691 °F

0.07 %

1.01 %

5.7 %

Characteristics and performance data
Measuring cycle time

< 500 ms

Step response time

9)

≤ 3 s

Max. filling/emptying speed

1 m/min

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value

always applies.
The measurement error from the process conditions is in the specified pressure and temperature

range of below 1 %.
Process pressure

-1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig),

depending on the process fitting

Vessel pressure relating to the flange

nominal stage

see supplementary instructions manual "Flanges ac-

cording to DIN-EN-ASME-JIS"

Process temperature (Clamp or flange

temperature)

-20 … +150 °C (-4 … +302 °F)

9)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk

solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).