11 Supplement

VEGAPULS 62 standpipe version • Profibus PA

36509-EN-121011

Gas phase

Temperature

Pressure

1 bar

(14.5 psig)

10 bar

(145 psig)

50 bar

(725 psig)

100 bar

(1450 psig)

200 bar

(2900 psig)

Steam (satu-

rated steam)

100 °C/212 °F 0.26 %

-

-

-

-

180 °C/356 °F 0.17 %

2.1 %

-

-

-

264 °C/507 °F 0.12 %

1.44 %

9.2 %

-

-

366 °C/691 °F 0.07 %

1.01 %

5.7 %

13.2 %

76.0 %

Characteristics and performance data
Measuring frequency

K-band (26 GHz technology)

Measuring cycle time

Ʋ Standard electronics approx.

450 ms

Ʋ Electronics with increased sensitivity

approx.

700 ms

Step response time

2)

≤ 3 s

Tracking speed of the measuring window

max.

1 m/min

Emitted HF power (depending on the parameter adjustment)

3)

Ʋ Average spectral transmission power

density

-14 dBm/MHz EIRP

Ʋ Max. spectral transmission power

density

+43 dBm/50 MHz EIRP

Ʋ Max. power density in a distance of

1 m

< 1 µW/cm²

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
For the process conditions, please also note the specifications on the type label. The lower value

always applies.

Seal

Antenna impedance

cone

Process temperature (measured on the process

fitting)

FKM (SHS FPM 70C3

GLT)

PFFE

-40 … +200 °C (-40 … +392 °F)

FFKM (Kalrez 6375)

PFFE

-20 … +200 °C (-4 … +392 °F)

FFKM (Kalrez 2035)

PFFE

-15 … +200 °C (5 … +392 °F)

FFKM (Kalrez 6230)

PFFE

-15 … +200 °C (5 … +392 °F)

Vessel pressure relating to the antenna

system

-1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psi)

2)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications until the output signal

has taken for the first time 90 % of the final value (IEC 61298-2).

3)

EIRP: Equivalent Isotropic Radiated Power