11 Supplement
VEGAPULS 61 • Foundation Fieldbus
36502-EN-121011
Ʋ H1 power supply
max. 32 (max. 10 with Ex)
Electrical protective measures
Protection, depending on housing version
Ʋ Plastic housing
IP 66/IP 67
Ʋ Aluminium housing, stainless steel
housing - investment casting, stain-
less steel housing - electro-polished
IP 66/IP 68 (0.2 bar)
4)
Ʋ Aluminium and stainless housing, in-
vestment casting (optionally available)
IP 66/IP 68 (1 bar)
Overvoltage category
III
Protection class
III
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.
They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as
well as under "Downloads" and "Approvals".
11.2 Supplementary information Foundation Fieldbus
The following table gives you an overview of the instrument versions and the corresponding device
descriptions, the electrical characteristics of the bus system as well as the applied function blocks.
Revisions Data
DD-Revision
Rev_01
CFF-File
010101.cff
Device Revision
0101.ffo
0101.sym
Cff-Revision
xx xx 01
Device software revision
> 4.4.0
ITK (Interoperability Test Kit) Number
5.0.2
Electricial Characteristics
Physicial Layer Type
Low-power signaling, bus-pow-
ered, FISCO I.S.
Input Impedance
> 3000 Ohms between
7.8 KHz - 39 KHz
Unbalanced Capacitance
< 250 pF to ground from either
input terminal
Output Amplitude
0.8 V P-P
Electrical Connection
2 Wire
Polarity Insensitive
Yes
Max. Current Load
10 mA
Device minimum operating voltage
9 V
4)