VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual
Page 65
65
11 Supplement
VEGAPULS 61 • Foundation Fieldbus
36502-EN-121011
Ʋ Max. power density in a distance of
1 m
< 1 µW/cm²
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specifications on the type label. The lower value
always applies.
Vessel pressure
Ʋ Encapsulated antenna system
-1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psi)
Ʋ Plastic horn antenna
-1 … 2 bar (-100 … 200 kPa/-14.5 … 29.0 psig)
Ʋ Version with adapter flange from
DN 150 PP
-1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)
Process temperature (measured on the
process fitting)
-40 … +80 °C (-40 … +176 °F)
Vibration resistance
Ʋ With adapter flange
2 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Ʋ with mounting strap
1 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Shock resistance
100 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
Ʋ Cable gland
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Cable entry
½ NPT
Ʋ Blind stopper
M20 x 1.5; ½ NPT
Ʋ Closing cap
M20 x 1.5; ½ NPT
Plug options
Ʋ Signal circuit
M12 x 1, according to ISO 4400, Harting HAN, 7/8" FF
Ʋ Indication circuit
M12 x 1
Wire cross-section (spring-loaded terminals)
Ʋ Massive wire, cord
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Electromechanical data - version IP 66/IP 68 (1 bar)
Options of the cable entry
Ʋ Cable gland with integrated connec-
tion cable
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Cable entry
½ NPT
Ʋ Blind stopper
M20 x 1.5; ½ NPT
Connection cable