beautypg.com

VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel 4 … 20 mA_HART - two-wire User Manual

Page 3

background image

3

Quick start

VEGAPULS 66 enamel • 4 … 20 mA/HART - two-wire

36527-EN-121011

3. Select in the menu item "Application" the vessel, the application

and the vessel form, for example, storage tank.

4. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

The radar sensor measures the distance from the sensor to the

product surface. For indication of the real level, an allocation of the

measured distance to the percentage height must be carried out.

100%

0%

1,5 m (59.1

")

15 m (590.6

")

2

1

Fig. 3: Parameterization example
1 Min. level = max. meas. distance

2 Max. level = min. meas. distance

For this adjustment, the distance is entered with full and virtually

empty vessel. If these values are not known, an adjustment with

distances, for example, of 10 % and 90 % is also possible. Starting

point for these distance specifications is always the seal surface of

the thread or flange.
1. In the menu "Additional settings", menu item "Damping" you have

to adjust the requested damping of the output signal.

2. Select the output characteristics in the menu item "Current out-

put".

The quick start is then finished. For further information see chapter

"Parameter adjustment".

Parameterization example

Further steps