beautypg.com

VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel 4 … 20 mA_HART - two-wire User Manual

Page 21

background image

21

4 Mounting

VEGAPULS 66 enamel • 4 … 20 mA/HART - two-wire

36527-EN-121011

For the parameter adjustment, select "Application standpipe" and

enter the tube diameter to compensate errors due to running time

shift

A false signal suppression with integrated sensor is recommended

but not mandatory

The measurement through a ball valve with complete run is pos-

sible

Constructional requirements on the bypass pipe:

Material metal, smoother inner tube

In case of an extremely rough tube inner surface, use an inserted

tube (tube in tube) or a radar sensor with tube antenna

Flanges are welded to the tube according to the orientation of the

polarisation level

Gap size with junctions ≤ 0.1 mm, for example, when using a ball

valve or intermediate flanges with single pipe sections

The antenna diameter of the sensor should correspond to the

inner diameter of the tube

Diameter should be constant over the complete length

Instruments for a temperature range up to 250 °C or up to 450 °C

have a distance piece between process fitting and electronics hous-

ing. Ths distance piece is used for thermal decoupling of the electron-

ics against high process temperatures.
Information:

The distance piece must only be incorporaed up to max. 50 mm in

the vessel installation. Only then, a reliable temperature decoupling is

guaranteed.

max. 50 mm (1.97"

)

1

2

3

Fig. 15: Mounting of the instrument with insulated vessels.
1 Electronics housing

2 Distance piece

3 Vessel insulation

Mounting in the vessel

insulation