VEGA VEGABAR 52 4 … 20 mA_HART - climate compensated User Manual

Page 53

background image

53

10 Supplement

VEGABAR 52 • 4 … 20 mA/HART - climate compensated

36718-EN-130321

Ʋ Turn down > 5 : 1

< 0.01 % x TD

Deviation with version 0.075 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.075 %

Ʋ Turn down > 5 : 1

< 0.015 % x TD

Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Deviation with absolute pressure measuring range 0.1 bar

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.25 %

Ʋ Turn down > 5 : 1

< 0.05 % x TD

Influence of the product or ambient temperature
Average temperature coefficient of the zero signal and the output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.

Nominal measuring range in

bar/kPa

Nominal

measuring

range in psig

Average temperature co-

efficient of the zero signal

and the output span, in

the compensated temper-

ature range 0 … +100 °C

(+32 … +212 °F), reference

temperature 20 °C (68 °F)

Average temperature coeffi-

cient of the zero signal and

the output span, outside

the compensated tempera-

ture range

0 … 0.2 bar/0 … 20 kPa

0 … 3 psig

< (0.15 + 0.4 x TD)%

< (0.15 + 0.6 x TD)%

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (0.15 + 0.4 x TD)%

< (0.15 + 0.6 x TD)%

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.1 + 0.2 x TD)%

< (0.1 + 0.3 x TD)%

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

< (0.1 + 0.2 x TD)%

< (0.1 + 0.3 x TD)%

0 … 5 bar/0 … 500 kPa

0 … 70 psig

< (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

0 … 10 bar/0 … 1000 kPa

0 … 150 psig < (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

0 … 25 bar/0 … 2500 kPa

0 … 350 psig < (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

0 … 60 bar/0 … 6000 kPa

0 … 900 psig < (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 0 bar/-100 … 0 kPa

-15 … 0 psig

< (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 1.5 bar/-100 … 150 kPa -15 … 25 psig < (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 5 bar/-100 … 500 kPa

-15 … 70 psig < (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 10 bar/-100 … 1000 kPa -

15 … 150 psig

< (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 25 bar/-100 … 2500 kPa -

15 … 350 psig

< (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%

-1 … 60 bar/-100 … 6000 kPa -

15 … 900 psig

< (0.05 + 0.1 x TD)%

< (0.1 + 0.15 x TD)%