beautypg.com

5 menu schematic – VEGA VEGABAR 53 Foundation Fieldbus User Manual

Page 35

background image

35

6 Set up with the display and adjustment module PLICSCOM

VEGABAR 53 • Foundation Fieldbus

36724-EN-130321

Reset
Basic adjustment
Peak value, measured value
Peak value, temperature

Basic adjustment

The "Reset" "Basic adjustment" resets the values of the following

menu items:

Menu section

Function

Reset value

Basic settings

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

0 s

Linearization

Linear

Sensor-TAG

Sensor

Display

Displayed value

AI-Out

The values of the following menu items are not reset with "Reset:

Menu section

Function

Reset value

Basic settings

Unit of measurement

No reset

Temperature unit

No reset

Position correction

No reset

Display

Backlight

No reset

Service

Language

No reset

Application

No reset

Default setting

Like basic adjustment, but in addition, special parameters are reset to

default values.

7)

Peak value

The min. and max. distance values are reset to the actual value.

Additional adjustment and diagnosis options such as e.g. scaling,

simulation or trend curve presentation are shown in the following

menu schematic. You will find a detailed description of these menu

items in the operating instructions manual "Display and adjustment

module".

6.5 Menu schematic

Information:

Depending on the version and application, the highlighted menu

windows may not always be available.

Optional settings

7)

Special parameters are parameters which are set customer-specifically on

the service level with the adjustment software PACTware.