2 supplementary information foundation fieldbus – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. Foundation Fieldbus User Manual
Page 51
51
11 Supplement
VEGAPULS 66 standpipe version • Foundation Fieldbus
36526-EN-121011
For that reason the associated approval documents of these instruments must be carefully noted.
They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as
well as under "Downloads" and "Approvals".
11.2 Supplementary information Foundation Fieldbus
The following table gives you an overview of the instrument versions and the corresponding device
descriptions, the electrical characteristics of the bus system as well as the applied function blocks.
Revisions Data
DD-Revision
Rev_01
CFF-File
010101.cff
Device Revision
0101.ffo
0101.sym
Cff-Revision
xx xx 01
Device software revision
> 4.4.0
ITK (Interoperability Test Kit) Number
5.0.2
Electricial Characteristics
Physicial Layer Type
Low-power signaling, bus-pow-
ered, FISCO I.S.
Input Impedance
> 3000 Ohms between
7.8 KHz - 39 KHz
Unbalanced Capacitance
< 250 pF to ground from either
input terminal
Output Amplitude
0.8 V P-P
Electrical Connection
2 Wire
Polarity Insensitive
Yes
Max. Current Load
10 mA
Device minimum operating voltage
9 V
Transmitter Function Blocks
Resource Block (RB)
1
Transducer Block (TB)
1
Standard Block (AI)
3
Execution Time
30 mS
Advanced Function Blocks
Discret Input (DI)
Yes
PID Control
Yes
Output Splitter (OS)
Yes
Signal Characterizer (SC)
Yes
Integrator
Yes
Input Selector (IS)
Yes
Arithmetic (AR)
Yes
Diagnostics
Standard
Yes
Advanced
Yes
Performance
No
Function Blocks Instantiable
No