VEGA VEGABAR 66 Foundation Fieldbus User Manual
Page 56
56
10 Supplement
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
Product temperature, suspension cable/measuring cell seal
Ʋ PE/FKM
-20 … +60 °C (-4 … +140 °F)
Ʋ PE/EPDM
-20 … +60 °C (-4 … +140 °F)
Ʋ PUR/FKM
-20 … +80 °C (-4 … +176 °F)
Ʋ PUR/EPDM
-20 … +80 °C (-4 … +176 °F)
Ʋ FEP/FKM
-20 … +100 °C (-4 … +212 °F)
Ʋ FEP/FFKM
-10 … +100 °C (+14 … +212 °F)
Ʋ FEP/EPDM
-20 … +100 °C (-4 … +212 °F)
Product temperature, connection tube/seal meas. cell
Ʋ FKM
-20 … +100 °C (-4 … +212 °F)
Ʋ FFKM
-10 … +100 °C (+14 … +212 °F)
Ʋ EPDM
-20 … +100 °C (-4 … +212 °F)
Product temperature, transmitter protection/seal meas. cell
Ʋ PVDF/FKM or EPDM
-20 … +60 °C (-4 … +140 °F)
Ʋ PVDF/FFKM
-10 … +60 °C (+14 … +140 °F)
Ʋ PE/FKM or EPDM
-20 … +60 °C (-4 … +140 °F)
Calibration position
upright, diaphragm points downward
Influence of the installation position
< 0.2 mbar/20 Pa (0.003 psig)
Vibration resistance
mechanical vibrations with 4 g and 5 … 100 Hz
15)
With version with connection tube, vibration resistance 1 g. With lengths > 0.5 m (1.64 ft) the tube
must be supported in addition.
Shock resistance
Acceleration 100 g/6 ms
16)
Electromechanical data - version IP 66/IP 67
Cable entry/plug
17)
Ʋ Single chamber housing
– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
– 1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
or:
– 2 x blind plug M20 x 1,5
15)
Tested according to the guidelines of German Lloyd, GL directive 2.
16)
Tested according to EN 60068-2-27.
17)
Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.