4 Mounting
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
Mount VEGABAR 66 with screwed connection as follows:
1. Weld the welded socket into the vessel top
2. Lower VEGABAR 66 to the requested height by means on the
welded socket G1½ or 1½ NPT on the vessel side
3. Insert the suspension cable from below into the open screwed
connection
4. Slide the seal cone and the cone sleeve over the suspension
cable, fasten manually with the seal screw
5. Screw the screwed connection into the socket, tighten with
SW 30 and then tighten seal screw with SW 19
How to correct the height:
1. Loosen seal screw with SW 19
2. Slide seal cone and cone sleeve to the requested position on the
cable
3. Fasten the seal screw
Removal is carried out in reverse order.
4.5 Mounting steps with lock fitting
1
3
2
4
5
Fig. 9: Lock fitting
1 Upper hexagon
2 Fixing screw
3 Washer disk
4 Lower hexagon
5 Fixing screw
Mount VEGABAR 66 with lock fitting as follows:
1. Weld the welded socket G1½ or 1½ NPT to the vessel top
2. Lower VEGABAR 66 through the welded socket.
- VEGABAR 25 (24 pages)
- VEGAFLEX 55K (32 pages)
- VEGABAR 17 (36 pages)
- D80 Hydrostatic pressure transmitters (40 pages)
- VEGAMET 513 (52 pages)
- D81 Hydrostatic pressure transmitter (44 pages)
- VEGASTAB 690 (12 pages)
- VEGASWING 83 fail safe and signal conditioning instrument VEGATOR 526 Ex (28 pages)
- VEGACONNECT 2 (4 pages)
- D81 METEC Hydrostatic pressure transmitter (44 pages)
- VEGAPULS 45 4 … 20 mA; HART compact sensor (72 pages)
- VEGAMET 515 (68 pages)
- VEGAFLEX 52K (32 pages)
- Capacitive electrodes EK Profibus PA (56 pages)
- VEGATOR 631 S1 (4 pages)
- VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire (68 pages)
- Capacitive electrodes EK 4 … 20 mA - Compact (40 pages)
- VEGABAR 65 4 … 20 mA_HART (76 pages)
- VEGABAR 64 Profibus PA (80 pages)
- VEGABAR 44 4 … 20 mA (28 pages)
- VEGADIS 50 Ex (8 pages)
- VEGAPULS 51V…54V (96 pages)
- VEGAFLEX 54P (Profibus PA) (48 pages)
- VEGASEL 643 (16 pages)
- VEGAPULS 56K (68 pages)
- VEGAFLEX 54K (36 pages)
- VEGABAR 41 HART (44 pages)
- VEGATOR 537 Ex (16 pages)
- VEGACAP 82-98 (36 pages)
- VEGADIS 371 Ex (20 pages)
- Capacitive electrodes EL Profibus PA (56 pages)
- VEGAFLEX 52V (36 pages)
- VEGAFLEX 51K (32 pages)
- VEGALOG 571 EP (Ex) (32 pages)
- D84 Hydrostatic pressure transmitter (44 pages)
- VEGABAR 64 Foundation Fieldbus (80 pages)
- VEGABAR 61 4 … 20 mA_HART (80 pages)
- VEGASCAN 850 (92 pages)
- VEGASON 54P…56P Profibus PA (68 pages)
- D77 Hydrostatic pressure transmitters (24 pages)
- VEGATRENN 546 Safety barrier type 146 (8 pages)
- VEGASON 71 - 1 … 75 - 1 (52 pages)
- VEGABAR 40 HART (40 pages)
- Capacitive electrodes EL … (44 pages)
- VEGABAR 24 (28 pages)