VEGA VEGABAR 66 Foundation Fieldbus User Manual
Page 47
47
8 Maintenance and fault rectification
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
•
F
T
: Temperature coefficient (influence of medium or ambient
temperature)
•
F
Kl
: Deviation
•
F
a
: Error current output
Level measurement 1500 mmWs
Product temperature 40 °C, reference temperature 20 °C
VEGABAR 66 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation ΔT: ΔT = 40 °C - 20 °C = 20 K
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
Basic accuracy digital output signal in percent:
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
)
F
T
= 0.05 %/10 K x TD
F
Kl
= 0.1 %
F
perf
= √((0.05 %/10 K x 20 K x 1.4)
2
+ (0.1 %)
2
)
F
perf
= 0.17 %
Total deviation digital output signal in percent:
F
total
= F
perf
+ F
stab
F
stab
= 0.1 %/year x TD
F
stab
= 0.1 %/year x 1.4
F
stab
= 0.14 %
F
total
= 0.17 % + 0.14 % = 0.31 %
Total deviation digital output signal absolute:
F
total
= 0.35 % x 147 mbar/100 % = 0.46 mbar = 4.7 mm
Basic accuracy analogue output signal in percent:
F
perf
= √((F
T
)
2
+ (F
Kl
)
2
+ (F
a
)
2
)
F
T
= 0.05 %/10 K x TD
F
Kl
= 0.1 %
F
a
= 0.15 %
F
perf
= √((0.05 %/10 K x 20 K x 1.4)
2
+ (0.1 %)
2
+ (0.15 %)
2
)
F
perf
= 0.23 %
Total deviation analogue output signal in percent:
F
total
= F
perf
+ F
stab
F
stab
= 0.1 %/year x TD
F
stab
= 0.1 %/year x 1.4
F
stab
= 0.14 %
F
total
= 0.23 % + 0.14 % = 0.37 %
Total deviation analogue output signal absolute:
F
total
= 0.37 % x 147 bar/100 % = 0.54 mbar = 5.5 mm
Example