VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 61
61
11 Supplement
VEGAPULS 63 • Profibus PA
36513-EN-130228
Gas phase
Temperature
Pressure
1 bar
(14.5 psig)
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
Air
20 °C/68 °F
0.00 %
0.22 %
1.2 %
2.4 %
4.9 %
200 °C/392 °F -0.01 %
0.13 %
0.74 %
1.5 %
3.0 %
400 °C/752 °F -0.02 %
0.08 %
0.52 %
1.1 %
2.1 %
Hydrogen
20 °C/68 °F
-0.01 %
0.10 %
0.61 %
1.2 %
2.5 %
200 °C/392 °F -0.02 %
0.05 %
0.37 %
0.76 %
1.6 %
400 °C/752 °F -0.02 %
0.03 %
0.25 %
0.53 %
1.1 %
Steam (satu-
rated steam)
100 °C/212 °F 0.26 %
-
-
-
-
180 °C/356 °F 0.17 %
2.1 %
-
-
-
264 °C/507 °F 0.12 %
1.44 %
9.2 %
-
-
366 °C/691 °F 0.07 %
1.01 %
5.7 %
13.2 %
76.0 %
Characteristics and performance data
Measuring frequency
K-band (26 GHz technology)
Measuring cycle time
Ʋ Standard electronics approx.
450 ms
Ʋ Electronics with increased sensitivity
approx.
700 ms
Step response time
1)
≤ 3 s
Beam angle
2)
Ʋ Clamp 2", 3"
18°
Ʋ Clamp 3½", 4"
10°
Ʋ Bolting DN 50
18°
Ʋ Bolting DN 80
10°
Ʋ flange DN 50, ANSI 2"
18°
Ʋ Flange DN 80 … DN 150, AN-
SI 3" … 6"
10°
Emitted HF power (depending on the parameter adjustment)
3)
Ʋ Average spectral transmission power
density
-14 dBm/MHz EIRP
Ʋ Max. spectral transmission power
density
+43 dBm/50 MHz EIRP
Ʋ Max. power density in a distance of
1 m
< 1 µW/cm²
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
1)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
2)
Outside the specified beam angle, the energy of the radar signal has a level which is reduced by 50 % (-3 dB)
3)
EIRP: Equivalent Isotropic Radiated Power