beautypg.com

VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 44

background image

44

6 Set up with the display and adjustment module

VEGAPULS 63 • Profibus PA

36513-EN-130228

module. The procedure is described in the operating instructions

manual "Display and adjustment module" in the menu item "Copy

sensor data". The data remain there permanently even if the sensor

power supply fails.
The following data or settings for adjustment of the display and ad-

justment module are saved:

All data of the menu "Setup" and "Display"

In the menu "Additional adjustments" the items "Sensor-specific

units, temperature unit and linearization"

The values of the user programmable linearization curve

The function can also be used to transfer settings from one instru-

ment to another instrument of the same type. If it is necessary to

exchange a sensor, the display and adjustment module is inserted

into the replacement instrument and the data are likewise written into

the sensor via the menu item "Copy sensor data".