6 Set up with the indicating and adjustment module

VEGAPULS 66 • Foundation Fieldbus

36522-EN-121011

Setup: Resetting of the parameter settings to the default values of

the respective instrument . Order-related settings remain but are

not taken over into the current parameters. User-generated false

signal suppression, user-programmed linearization curve, meas-

ured value memory, echo curve memory as well as event memory

remain untouched. The linearization is set to linear.

False signal suppression: Deleting a previously created false

signal suppression. The false signal suppression created in the

factory remains active.

Peak values measured value: Resetting of the measured min.

and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 66:

Menu section

Menu item

Default value

Setup

Measurement

loop name

Sensor

Medium

Liquid/Water
Bulk solids/Crushed stones, gravel

Applications

Storage tank
Silo

Vessel form

Vessel bottom, dished boiler end
Vessel top, dished boiler end

Vesell height/

Measuring range

Recommended measuring range, see

"Technical data" in the supplement

Min. adjustment

Recommended measuring range, see

"Technical data" in the supplement

Damping

0.0 s

Display

Language

Like order

Displayed value

Distance

Display unit

m(d)

Scaling

0.00 %, 0 l
100.00 %, 100 l

Additional adjust-

ments

Distance unit

m

Temperature unit °C
Unit SV2

m

Probe length

Length of the standpipe Ex factory

Linearisation

curve

Linear

6.4 Saving the parameter adjustment data

We recommended noting the adjusted data, e.g. in this operating

instructions manual, and archiving them afterwards. They are thus

available for multiple use or service purposes.