beautypg.com

Quick start – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 2

background image

2

Quick start

VEGAPULS 66 • Foundation Fieldbus

36522-EN-121011

Quick start

The quick start enables a quick setup with many applications. You

can find further information in the respective chapters of the operating

instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should

protrude > 10 mm into the vessel

> 500 mm

(19.69")

ca. 10 mm

Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

2. Note min. socket diameter depending on the socket length
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

1

2

( )

(-)

1

5

0

1

0

1

+

6 7 8

Bus

2
3

4

5

Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 Contact pins for the indicating and adjustment module or interface adapter

3 Simulation switch ("1" = mode for simulation release)

4 For external indicating and adjustment unit

5 Ground terminal for connection of the cable screen

For further information see chapter "Connecting to power supply".
1. Go via the indicating and adjustment module to the menu "Setup".

2. In the menu item "Medium"you select the medium of your applica-

tion, for example "Aqueous solution".

Mounting

Connect electrically

Set parameters