beautypg.com

VEGA VEGABAR 53 4 … 20 mA_HART User Manual

Page 57

background image

57

10 Supplement

VEGABAR 53 • 4 … 20 mA/HART

36722-EN-130321

Ʋ Non-Ex instrument

20 … 36 V DC

Ʋ Ex-ia instrument

20 … 30 V DC

Ʋ Exd instrument

20 … 36 V DC

Permissible residual ripple

Ʋ < 100 Hz

U

ss

< 1 V

Ʋ 100 Hz … 10 kHz

U

ss

< 10 mV

Load

see diagram

1000

750

500

250

14

18

16

20

22

24

26

28

30

32

34

36

V

4

1

2

3

Fig. 29: Voltage diagram
1 HART load

2 Voltage limit Ex-ia instrument

3 Voltage limit non-Ex/Ex-d instrument

4 Operating voltage

Electrical protective measures
Protection rating

Ʋ Housing, standard

IP 66/IP 67

23)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

24)

Ʋ Process component in IP 68 version IP 68 (25 bar)

Ʋ External housing

IP 65, IP 66/IP 68 (0.2 bar)

Overvoltage category

III

Protection class

II

Functional safety (SIL)
Functional safety is already activated on instruments with SIL qualification ex factory. On instru-

ments without SIL qualification ex factory, the functional safety must be activated by the user via

the display and adjustment module or via PACTware for applications according to SIL.

Functional safety according to IEC 61508-4

Ʋ Single channel architecture (1oo1D) up to SIL2

23)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

24)

Only with instruments with absolute pressure ranges.