VEGA VEGABAR 53 4 … 20 mA_HART User Manual
Page 36
36
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 53 • 4 … 20 mA/HART
36722-EN-130321
Caution:
Note the following if the VEGABAR 53 with corresponding approval is
used as part of an overfill protection system according to WHG (Water
Resources Act):
If a linearization curve is selected, the measuring signal is no longer
linearly proportional to the level. This must be taken into consideration
by the user, particularly when setting the switching point on the limit
signal indicator.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
•
Measured value presentation
•
Adjustment
•
Damping
•
Linearization curve
•
Sensor-TAG
•
Displayed value
•
Display unit
•
Scaling
•
Current output
•
Unit of measurement
•
Language
The following safety-relevant data are not read out or written:
•
SIL
•
HART mode
6)
•
PIN
•
Application
Copy sensor data
Copy sensor data?
Basic adjustment
The reset function resets all parameters adjusted by the user to the
delivery status and the peak values to the actual values.
Reset
Select reset?
▼
Reset
Basic adjustment
Peak value, measured value
Peak value, temperature
Copy sensor data
Reset
6)
With instruments with signal output 4 … 20 mA/HART