VEGA VEGABAR 53 4 … 20 mA_HART User Manual
Page 54
54
10 Supplement
VEGABAR 53 • 4 … 20 mA/HART
36722-EN-130321
Ambient conditions
Ambient, storage and transport temperature
Ʋ Standard version
-40 … +80 °C (-40 … +176 °F)
Ʋ Connection G1 A front-flush according
to EHEDG
-10 … +80 °C (+14 … +176 °F)
Ʋ Version for oxygen applications
13)
-40 … +60 °C (-40 … +140 °F)
Ʋ Versions IP 66/IP 68 (1 bar) and IP 68
(25 bar), connection cable PUR
-20 … +80 °C (-4 … +176 °F)
Ʋ Version IP 66/IP 68 (1 bar), connec-
tion cable PE
-20 … +60 °C (-4 … +140 °F)
Process conditions
The specifications of the pressure stage and product temperature are used as an overview. The
specifications on the type label are applicable.
Pressure stage, process fitting
Ʋ Thread 316L, depending on connec-
tion
PN 60, PN 600, PN 1000
Ʋ Hygienic fittings 316L, depending on
connection
PN 6, PN 10, PN 25, PN 40 (PN 40 only with DRD and
DIN 11851)
Ʋ Flange 316L
PN 16/PN 40 or 150 lb/300 lb
Product temperature, depending on the sealing
14)
Ʋ Without sealing (with process fitting
according to EN 837)
-40 … +105 °C (-40 … +221 °F)
Ʋ FKM (VP2/A)
-20 … +105 °C (-4 … +221 °F)
Ʋ EPDM (A+P 75.5/KW75F)
-40 … +105 °C (-40 … +221 °F)
Ʋ NBR (COG)
-20 … +105 °C (-4 … +221 °F)
Product temperature threaded fitting M44 x 1.25 as well as hygienic fittings, dependent on the seal-
ing
15)16)
Ʋ Without sealing
-30 … +150 °C (-22 … +302 °F)
Ʋ FKM (VP2/A)
-20 … +150 °C (-4 … +302 °F)
Ʋ EPDM (A+P 75.5/KW75F)
-30 … +150 °C (-22 … +302 °F)
Ʋ NBR (COG)
-20 … +150 °C (-4 … +302 °F)
Vibration resistance
mechanical vibrations with 4 g and 5 … 100 Hz
17)
Vibration resistance - Version with double
chamber housing of stainless steel
mechanical vibrations with 2 g and 5 … 100 Hz
18)
Vibration resistance - Versions up to
+150 °C (+302 °F)
mechanical vibrations with 0.7 g and 5 … 100 Hz
19)
13)
Up to 60 °C (140 °F).
14)
Version for oxygen applications up to 60 °C (140 °F).
15)
Hygienic fitting LA/LB up to +105 °C (+221 °F)
16)
Version for oxygen applications up to +60 °C (+140 °F).
17)
Tested according to the guidelines of German Lloyd, GL directive 2.
18)
Tested according to the guidelines of German Lloyd, GL directive 2.
19)
Tested according to the guidelines of German Lloyd, GL directive 2.