2 information on profibus pa – VEGA VEGABAR 55 Profibus PA - climate compensated User Manual

Page 54

background image

54

10 Supplement

VEGABAR 55 • Profibus PA - climate compensated

39442-EN-130321

Electrical protective measures
Protection rating

Ʋ Housing, standard

IP 66/IP 67

15)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

16)

Ʋ Process component in IP 68 version IP 68 (25 bar)

Ʋ External housing

IP 65, IP 66/IP 68 (0.2 bar)

Overvoltage category

III

Protection class

II

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

10.2 Information on Profibus PA

Instrument master file

The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.

These data are, e.g. the permissible transmission rates as well as information on diagnostics values

and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-

cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-

ment in the configuration tool.

Ident number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. For VEGABAR 55

the ID number is 0 x 076F(hex) and the GSD file BR__076F.GSD. As an option to this manufactur-

er-specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGABAR

55 you have to use the general GSD file PA139701.GSD. If the general GSD file is used, the sensor

must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-

ates with the manufacturer-specific ID number.

Note:

When using the profile-specific GSD file, the PA-OUT value as well as the temperature

value are transmitted to the PLC (see block diagram "Cyclical data traffic").

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-

tion. The below block diagram below shows which data can be accessed by the PLC.

15)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

16)

Only with instruments with absolute pressure ranges.