VEGA VEGABAR 55 Profibus PA - climate compensated User Manual
Page 50
50
10 Supplement
VEGABAR 55 • Profibus PA - climate compensated
39442-EN-130321
Nominal measuring range in
bar/kPa
Nominal
measuring
range in psig
Average temperature coef-
ficient of the zero signal, in
the compensated temper-
ature range 0 … +100 °C
(+32 … +212 °F), reference
temperature 20 °C (68 °F)
Average temperature co-
efficient of the zero signal,
outside the compensated
temperature range
0 … 0.2 bar/0 … 20 kPa
0 … 3 psig
< (0.05 + 0.05 x TD)%/10K
< (0.05 + 0.1 x TD)%/10K
0 … 0.4 bar/0 … 40 kPa
0 … 6 psig
< (0.05 + 0.05 x TD)%/10K
< (0.05 + 0.1 x TD)%/10K
0 … 1 bar/0 … 100 kPa
0 … 15 psig
< (0.02 + 0.05 x TD)%/10K
< (0.02 + 0.1 x TD)%/10K
0 … 2.5 bar/0 … 250 kPa
0 … 35 psig
< (0.02 + 0.05 x TD)%/10K
< (0.02 + 0.1 x TD)%/10K
0 … 5 bar/0 … 500 kPa
0 … 70 psig
< (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
0 … 10 bar/0 … 1000 kPa
0 … 150 psig < (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
0 … 25 bar/0 … 2500 kPa
0 … 350 psig < (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-1 … 0 bar/-100 … 0 kPa
-15 … 0 psig
< (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-1 … 1.5 bar/-100 … 150 kPa -15 … 25 psig < (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-1 … 5 bar/-100 … 500 kPa
-15 … 70 psig < (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-1 … 10 bar/-100 … 1000 kPa -
15 … 150 psig
< (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-1 … 25 bar/-100 … 2500 kPa -
15 … 350 psig
< (0.02 + 0.03 x TD)%/10K
< (0.04 + 0.06 x TD)%/10K
-0.1 … 0.1 bar/-10 … 10 kPa
-
1.5 … 1.5 psig
< (0.05 + 0.05 x TD)%/10K
< (0.05 + 0.1 x TD)%/10K
-0.2 … 0.2 bar/-20 … 20 kPa
-3 … 3 psig
< (0.05 + 0.05 x TD)%/10K
< (0.05 + 0.1 x TD)%/10K
-0.5 … 0.5 bar/-50 … 50 kPa
-7 … 7 psig
< (0.05 + 0.05 x TD)%/10K
< (0.02 + 0.1 x TD)%/10K
Thermal change of the current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output
< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C
(-40 … +176 °F)
0,15 %
-0,15 %
-40°C
-20°C
20°C
40°C
60°C
80°C
Fig. 28: Thermal change, current output
Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital HART interface as well as to analogue current output 4 … 20 mA under refer-
ence conditions. Specifications refer to the set span. Turn down (TD) is the relation nominal meas-
uring range/set span.