beautypg.com

4 measurement error with constant level, 4 measurement error during filling, 4 measurement error during emptying – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. 4 … 20 mA_HART - four-wire User Manual

Page 40

background image

40

9 Diagnosis, Asset Management and service

VEGAPULS 62 standpipe version • 4 … 20 mA/HART - four-wire

36508-EN-121011

9.4 Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value

shows a too low or too

high level

Level

time

0

– Min./max. adjustment not

correct

– Adapt min./max. adjustment

– Wrong linearization curve

– Adapt linearization curve

– Installation in a bypass tube or

standpipe, hence running time

error (small measurement error

close to 100 %/large error close

to 0 %)

– Check parameter "Application"

with respect to vessel form,

adapt if necessary (bypass,

standpipe, diameter)

2. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out false signal suppres-

sion

– Amplitude or position of a

false echo has changed (e.g.

condensation, buildup); false

signal suppression no longer

matches

– Determine the reason for the

changed false echo, carry out

false signal suppression, e.g.

with condensation

9.4 Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3. Measured value re-

mains in the area of the

bottom during filling

Level

time

0

– Echo from the tank bottom

larger than the product echo,

for example, with products with

ε

r

< 2.5 oil-based, solvents

– Check application parameters

Medium, Vessel height and

Floor form, adapt if necessary

4. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to foam generation or false

echoes in the close range. The

sensor goes into overfill protec-

tion mode. The max. level (0 m

distance) as well as the status

message "Overfill protection"

are outputted.

– Check measuring site: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Use a sensor with a more suit-

able antenna

9.4 Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

5. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering instal-

lations in the close range by

changing the polarization

direction

– After removing the false ech-

oes, the false signal suppres-

sion must be deleted. Carry out

a new false signal suppression