6 Set up with the indicating and adjustment module

VEGAPULS 62 standpipe version • 4 … 20 mA/HART - four-wire

36508-EN-121011

With radar sensors with standpipe antenna, the sensor length is

already preset in this menu item. When shortening the standpipe

antenna afterwards, this value must be appropriately corrected.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and

laboratory parameters to the default values of the respective instru-

ment. A created false signal suppression, user programmable lineari-

zation curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the

respective instrument in the menu item Setup. User-generated false

signal suppression, user-programmed linearization curve, measured

value memory as well as event memory remain untouched. The

linearization is set to linear.
False signal suppression: Deleting a previously created false signal

suppression. The false signal suppression created in the factory

remains active.
Peak values distance: Resetting the measured min. and max. dis-

tances to the actual measured value.
The following table shows the default values of the instrument. De-

pending on the instrument version, not all menu items are available or

differently assigned:

Menu

Menu item

Default value

Setup

Measurement

loop name

Sensor

Min. adjustment

Length of the standpipe Ex factory

Max. adjustment

0.000 m

Damping

0.0 s

Current output

mode

4 … 20 mA, < 3.6 mA

Current output

Min./Max.

Min. current 3.8 mA, max. current

20.5 mA

Additional adjustments/

Probe length

Additional adjustments

- Reset