5 Connecting to the bus system
VEGAPULS 66 standpipe version • Profibus PA
36525-EN-121011
Contact pin
Colour connection ca-
ble in the sensor
Terminal, electronics
module
Pin 3
Blue
7
Pin 4
Black
8
5.6 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 11: Wire assignment fix-connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.7 Set instrument address
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nection to a Profibus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The indicating and adjustment module (address setting via soft-
ware)
•
PACTware/DTM (address setting via software)
The hardware addressing is effective if an address <126 is adjusted
with the address selection switches on the instrument. Hence the
software addressing is no longer effective, the adjusted hardware
address is valid.
Wire assignment, con-
nection cable
Instrument address
Hardware addressing