9 Diagnosis, Asset Management and service

VEGAPULS SR 68 • Profibus PA

38296-EN-130624

Maintenance: Due to external influences, the instrument function

is limited. The measurement is affected, but the measured value is

still valid. Plan in maintenance for the instrument because a failure is

expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.

The following table shows the error codes in the status message

"Failure" and gives information on the reason and rectification. Keep

in mind that some information is only valid with four-wire instruments.

Code
Text mes-

sage

Cause

Rectification

F013
no measured

value avail-

able

– Sensor does not detect an

echo during operation

– Antenna system contami-

nated or defective

– Check or correct installation

and/or parameter adjust-

ment

– Clean or exchange process

component or antenna

F017
Adjustment

span too small

– Adjustment not within

specification

– Change adjustment accord-

ing to the limit values (dif-

ference between min. and

max. ≥ 10 mm)

F025
Error in the

linearization

table

– Index markers are not con-

tinuously rising, for examle

unlogical value pairs

– Check linearization table

– Delete table/Create new

F036
No operable

software

– Failed or interrupted soft-

ware update

– Repeat software update

– Check electronics version

– Exchanging the electronics

– Send instrument for repair

F040
Error in the

electronics

– Hardware defect

– Exchanging the electronics

– Send instrument for repair

F080

– General software error

– Separate operating voltage

briefly

F105
Determine

measured

value

– The instrument is still in the

start phase, the measured

value could not yet be

determined

– Wait for the end of the

switch-on phase

– Duration depending on

the version and parameter

adjustment up to approxi-

mately 3 min.

F113
Communica-

tion error

– EMC interferences

– Transmission error with the

external communication

with 4-wire power supply

unit

– Remove EMC influences

– Exchange 4-wire power

supply unit or electronics

F125
Unpermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

Failure