2 connecting – VEGA VEGAPULS SR 68 Profibus PA User Manual
Page 31
31
5 Connecting to power supply
VEGAPULS SR 68 • Profibus PA
38296-EN-130624
ceramic capacitor (e.g. 1 nF, 1500 V). Low-frequency potential equali-
sation currents are thus suppressed, but the protective effect against
high frequency interference signals remains.
5.2 Connecting
The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.
The connection to the display and adjustment module or to the inter-
face adapter is carried out via contact pins in the housing.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.
Proceed as follows:
1. Unscrew the housing cover
2. If a display and adjustment module is installed, remove it by turn-
ing it slightly to the left.
3. Loosen compression nut of the cable entry
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry
Fig. 27: Connection steps 5 and 6 - Single chamber housing
Connection technology
Connection procedure