9 Diagnosis, Asset Management and service
VEGAPULS 63 • 4 … 20 mA/HART two-wire
36511-EN-130228
Code
Text mes-
sage
Cause
Rectification
M501
Error in the
non-active
linearization
table
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M502
Error in the
diagnosis
memory
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M503
Reliability too
low
– The echot/noise ratio is the
small for a reliable meas-
urement
– Check installation and
process conditions
– Clean the antenna
– Change polarisation direc-
tion
– Use instrument with higher
sensitivity
M504
Error on an
device inter-
face
– Hardware defect
– Check connections
– Exchanging the electronics
– Send instrument for repair
M505
No echo avail-
able
– Level echo can no longer
be detected
– Clean the antenna
– Use a more suitable
antenna/sensor
– Remove possible false
echoes
– Optimize sensor position
and orientation
9.4 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
The first measures are:
•
Evaluation of fault messages, for example via the display and
adjustment module
•
Checking the output signal with 4 … 20 mA instruments
•
Treatment of measurement errors
Further comprehensive diagnostics options offer a PC with the soft-
ware PACTware and the suitable DTM. In many cases, the reasons
can be determined in this way and faults can be rectified.
Connect a handmultimeter in the suitable measuring range according
to the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:
Reaction when malfunc-
tions occur
Procedure for fault recti-
fication
Check the 4 … 20 mA
signal