9 Diagnosis, Asset Management and service

VEGAPULS 63 • 4 … 20 mA/HART two-wire

36511-EN-130228

Code
Text mes-

sage

Cause

Rectification

F264
Installation/

Setup error

– Adjustment not within the

vessel height/measuring

range

– Max. measuring range of

the instrument not sufficient

– Check or correct installation

and/or parameter adjust-

ment

– Use an instrument with big-

ger measuring range

F265
Measurement

function dis-

turbed

– Sensor no longer carries

out a measurement

– Operating voltage too low

– Check operating voltage

– Carry out a reset

– Separate operating voltage

briefly

The following table shows the error codes and text messages in the

status message "Function check" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

C700
Simulation ac-

tive

– A simulation is active

– Finish simulation

– Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the

status message "Out of specification" and provides information on

causes as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

S600
Unpermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

S601
Overfilling

– Danger of vessel overfilling

– Make sure that there is no

further filling

– Check level in the vessel

The following table shows the error codes and text messages in the

status message "Maintenance" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

M500
Error with the

reset delivery

status

– With the reset to delivery

status, the data could not

be restored

– Repeat reset

– Load XML file with sensor

data into the sensor

Function check

Out of specification

Maintenance