beautypg.com

VEGA SOLITRAC 31 4 … 20 mA_HART - four-wire User Manual

Page 48

background image

48

6 Set up with the display and adjustment module

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

In this menu item you can also define the switching behaviour in case

of fault. You can select if the current output should output 22 mA or

< 3.6 mA in case of fault.

In this menu item you can select which mode the sensor should oper-

ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.
Overfill protection = the relay will deenergise (safe condition) when

the max. level is reached.
Dry run protection = the relay will deenergise (safe condition) when

the min. level is reached.
Make sure that you have selected the correct characteristics. See

menu item "Setup/Current output mode".

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual

"Display and adjustment module".
Display

With this parameter you can change the display language.

This parameter is described in the operating instructions manual

"Display and adjustment module".

With this parameter you can change the indication of the display.

You can choose if the display should show the actual pulse rate or the

electronics temperature.

Diagnostics
In this menu item, you can enquire the status of your sensor. In normal

operation, the sensor displays the message "OK". In case of fault, you

will find the corresponding fault code here.
This parameter is described in the operating instructions manual

"Display and adjustment module".

Setup/Relay

Lock setup - adjustment

Display - Language

Display/Displayed value

Diagnostics - Device

status