6 Set up with the display and adjustment module

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

40090-EN-131119

Note:

If you cannot fill the vessel during the adjustment procedure to at least

60 % of the max. level, it is possible to carry out the full adjustment

by switching off the radiation. The switched-off radiation simulates a

100 % filling.
Because you have already set the background radiation to 0 in the

menu item: "Setup/Background radiation", the measured pulse rate

must be around 0 ct/s.
Show diagram
This menu item is only available if a linearization was already carried

out.

Show table
In this menu item you can show the individual value pairs of the

linearization.

Linearization - Delete
You can also delete individual linearization points.

Linearization - Modify
You can also modify individual linearization points.

In this menu item you can adjust the damping of the sensor. With

it you can suppress fluctuations in the measured value indication,

caused e.g. by an agitated product surface. This time can be between

1 and 1200 seconds. Keep in mind that the reaction time also in-

creases and the instrument reacts to quick level changes with a delay.

Generally a time of approximately 60 seconds is sufficient to smooth

the measured value indication.

Setup/Damping