beautypg.com

VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual

Page 65

background image

65

11 Supplement

VEGAPULS 62 • Profibus PA

36505-EN-121011

Number of FBs with AI (function blocks

with analogue input)

3

Default values

Ʋ 1. FB

PV

Ʋ 2. FB

SV 1

Ʋ 3. FB

SV 2

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex-d instruments

16 mA, ±0.5 mA

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

- 10 mm (- 0.394 in)

0

1 2

3

Fig. 56: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Reproducibility

≤ ±1 mm

Deviation with bulk solids

The values depend to a great extent on the application.

Binding specifications are thus not possible.

Variables influencing measurement accuracy
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm