VEGA VEGABAR 63 Profibus PA User Manual
Page 47
?
Wrong presentation of the measured value in Simatic S5
l
Simatic S5 cannot interpret the number format IEEE of the
measured value
à Insert converting component from Siemens
?
In Simatic S7 the measured value is always presented as 0
l
Only four bytes are consistently loaded in the PLC
à Use function component SFC 14 to load 5 bytes consistently
?
Measured value on the indicating and adjustment module does not
correspond to the value in the PLC
l
The menu item "Display - Display value" is not set to "PA-Out"
à Check values and correct, if necessary
?
No connection between PLC and PA network
l
Incorrect adjustment of the bus parameter and the segment
coupler-dependent baud rate
à Check data and correct, if necessary
?
Instrument does not appear during connection setup
l
Profibus DP cable pole-reversed
à Check cable and correct, if necessary
l
Incorrect termination
à Check termination at the beginning and end points of the bus
and terminate, if necessary, according to the specification
l
Instrument not connected to the segment, double assignment
of an address
à Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
10)
à Exchange instrument or return instrument for repair
?
E
017
l
Adjustment span too small
à repeat with modified values
?
E
036
l
no operable sensor software
à Carry out a software update or send the instrument for repair
10)
Fault message can also appear if the pressure is higher than the nominal
range.
Fault messages via the
indicating/adjustment
module
VEGABAR
63 • Profibus PA
47
8 Maintenance and fault rectification
32463
-
EN
-081209