VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) enamel Foundation Fieldbus User Manual
Page 50
Reference conditions to measuring accuracy (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
-
Temperature
+18
… +30 °C (+64 … +86 °F)
-
Relative humidity
45 … 75 %
-
Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Other reference conditions
-
Reflector
ideal reflector, e.g. metal plate 2 x 2 m
-
False reflections
Biggest false echo, 20 dB smaller than the useful
echo
Characteristics and performance data
Frequency
C-band (6 GHz technology)
Beam angle 3 dB, depending on the antenna system
-
without horn antenna
38°
-
ø
75 mm (2.953 in)
38°
-
ø
96 mm (3.78 in)
30°
-
ø
146 mm (5.748 in)
20°
-
ø
196 mm (7.717 in)
17°
-
ø
242 mm (9.528 in)
14°
Step response or adjustment time
4)
> 1
s (dependent on the parameter setting)
Max. level change
adjustable up to 1 m/min. (dependent on the
parameter adjustment)
Max. emitted HF power of the antenna system
-
Pulse peak power approx.
0.1 mW
-
Pulse duration
< 2
ns
-
SAR value
5)
0.471 mW/kg
Measuring accuracy
Resolution, general
max. 1 mm (0.039 in)
Deviation
6)
see diagrams
4)
Time to output the correct level (with max. 10 % deviation) after a sudden
level change.
5)
at the aperture of a horn antenna with ø 150 mm
6)
Incl. non-linearity, hysteresis and non-repeatability.
50
VEGAPULS
66 enamel • Foundation Fieldbus
10 Supplement
33336
-EN
-090305