VEGA VEGAFLEX 61 4 … 20 mA_HART four-wire User Manual
Page 46
C
ycle time
min. 1 s (dependent on the parameter setting)
S
ignal resolution
1.6 µA
F
ailure signal current output (adjustable)
mA value unchanged 20.5 mA, 22 mA, < 3.6 mA
(
adjustable)
M
ax. output current
22
mA
L
oad
<
500 Ω
3)
D
amping (63 % of the input variable)
0 … 999
s, adjustable
F
ulfilled NAMUR recommendations
NE
43
HART
output values
-
1. HART
value (Primary Value)
D
istance to the level
-
2. HART
value (Secondary Value)
D
istance to the level - scaled (for example hl, %)
R
esolution, digital
>
1
mm (0.039 in)
Accuracy (similar to DIN EN 60770-1)
P
rocess reference conditions according to DIN EN 61298-1
-
T
emperature
+
18 … +30 °C (+64 … +86 °F)
-
R
elative humidity
45 … 75 %
-
A
ir pressure
+
860 … +1060
mbar/+86 … +106 kPa
(+12.5 … +15.4
psig)
I
nstallation reference conditions
-
M
in. distance to installations
>
500
mm (19.69 in)
-
V
essel
metallic, ø 1 m (3.281 ft), centric installation,
process fitting flush with the vessel ceiling
-
M
edium
W
ater/Oil (Dk value ~2.0)
-
I
nstallation
P
robe end does not touch the vessel bottom
S
ensor parameter adjustment
G
ating out of false signals carried out
I
n bulk solids applications, implementing a false
signal suppression is generally not recommended.
T
he accuracy of bulk solid applications depends
considerably on the application. Hard and fast
accuracy specifications are thus not available.
D
eviation
see diagrams
D
epending on the installation conditions, there can
be deviations which can be rectified with an
adaptation of the adjustment or a change of the
measured value offset in the DTM service mode.
3)
W
ith inductive load ohmic share min. 25 Ω/mH.
46
VEGAFLEX
61 • 4 … 20
mA/HART four-wire
10 S
upplement
31834
-EN
-100426